Products

Home

 

Quality Lineup:

Voltage Amps Model # Banks *Case Size Weight (lbs - kilo)
12 20

35

50

75

100

12202

12352

12502

12753

121003

3

3

3

3

3

2

2

23

3

3

37 - 16.8

39 - 17.5

52 - 23.2

92 - 41.8

101 - 45.4

24 15

30

50

75

100

24152

24302

24503

24753

241003

3

3

3

3

3

2

2

3

3

3

37 - 16.8

52 - 21.4

85 - 38.6

115 - 52.4

135 - 52.3

32/36 20

30

50

32202

32302

32503

3

3

3

2

2

3

46 - 20.9

53 - 38.6

104 - 47.3

48 10

40

48102

48403

3

3

2

3

42 - 19.1

115 - 52.3

*Case Size Height (in) Width (in) Depth (in)
2 10 10 10
3 18 16 10

Custom Constant Volt Chargers built to users specifications of voltage and current are available Call for quotation!

Quality Options:

Option Part # Description
Remote Failure Alarm RFA-OPTION Form C Relays, Signals DC output and/or AC input failure.
VMI Control Board 300-2600-00 Un-Configured universal smart charge control printed circuit board, compatible with any VMI or upgraded older McCarron or Ratelco VM charger.
Factory Configured VMI Control Board 300-2600-FC Same as VMI Control Board but factory configured for voltage and amperage output. Specify voltage and amperage output when ordered.
Ratelco Retro-Fit Kit 300-2600-KT Upgrade older McCarron or Ratelco VM chargers to Smart Charge. Features include: Float/Equalize voltage adjustments, equalize time control, soft start, cross talk elimination, and 1/2 of 1% voltage regulation. Kit includes: 300-2600-FC circuit board, lighted FL/EQ switch, decal, and complete instructions. 
VMI Remote Kit   Ammeter and FL/EQ switch with equalize indicator light. Panel NOT included.
VMI BFS-KIT   Battery Fail Safe Compensation Kit, included in all 2008 models. Protects VMI control PCB and connected equipment from elevated AC ripple due to dead batteries, cell shorts, and accidental battery disconnection. Improved EMI properties. Recommended instructions included.

Quality Features:

Multiple Battery Compatibility: Compatible with the most popular battery types: lead acid, VRLA, lead calcium, gel cell, flooded or sealed...
Extended Battery Life: When properly configured, proven to extend the life of the battery through precise regulation and charge algorithm.
100% Continuous Output: At rated voltage, at 50 deg C, convection cooled, with no temperature degradation.
Precise Constant Voltage Regulation: 1/2 of 1%, no load to full load.
Isolation Transformer: Input: 50/60 Hz; 120, 208, 220, 240 VAC, single phase.
3 Bank Capability: Diode isolated output that will maintain 3 separate battery banks.
Reverse Polarity Protected.
Independently Adjustable Voltage Settings: Float and Equalize/Recharge settings independently adjustable for all popular battery types.
Soft Start: Protects connected loads from surges.
Cycle Time Control: For Equalize/Recharge cycle, 0 - 140 hrs, user selectable.
Surge Damped: 50% load change response time less than 2 seconds.
Ignition Protected: AC and DC reset breakers (48v DC output is fused).
Remote Monitoring Connection Points: For FL/EQ toggle, ammeter and optional failure alarms.
Power Up Options: In Float or Equalize, user selectable.
Lighted Indicating Push Button: Toggle between Float and Equalize.
35+ Year Life Expectancy.
Standards Compliant: Built to meet applicable UL, CSA, standards for ABYC, DNV, ABS, and USCG installation requirements.
Drip Proof Enclosure: Meets UL 1236 for drip proof requirements.
Installation Kit Included: "No Flange" easy mount installation kit.

 